LT Swithed Type Capacitor Banks (Automatic)
                     
 

    3 KVAr single phase capacitor banks.
    These units are connected in delta formation.
    ACV_ Automatic Control Unit.
    This special unit will monitor total load KVAr on the secondary side of the transformer and will automatically switch ON or switch OFF the capacitors banks in accordance with the settings.
    ACU will automatically switch off the contactor whenever it forces an impending danger such as
  • Voltage 10% above 415 V (however it will resume function after the excessive voltage has dropped to 5% above 415 V)
  • Voltage 35% below 415 V (functions again when low voltage has risen to 25% below 415 V)
  • When load current imbalance between two phases cross the limit of 50% of the lowest current of the 3 phases.
  • Opening of relevant capacitors when the rated current 30% remains consistent for a period of 30 Mts. inspite of few fluctuations.
  • In case of error in the operations ACU will not switch ON until the fault is rectified.
     
  ELECTRO CAPACITORS CIRCUIT DIAGRAM
















    